Direct-to-chip cooling vendors
Direct-to-chip cooling bolts a cold plate onto each GPU and CPU and pumps coolant through it, carrying most of the server’s heat out as liquid. Server makers build their densest racks around it: Dell rates its IR7000 rack at 504 kW with direct liquid cooling, and Supermicro’s DLC-2 rack runs an in-rack CDU of 250 kW. Cold plates come from specialists such as CoolIT, JetCool and Chilldyne, from two-phase makers ZutaCore and Accelsius, and from Taiwanese suppliers Cooler Master and AVC.
| Technologies | GPU platforms (vendor-stated) | Coolant | ||||||
|---|---|---|---|---|---|---|---|---|
| Supermicro | CDU · D2C · Sidecar · Manifold · OEM | 5,0001 | 2502 | NVIDIA GB200 NVL72; NVIDIA HGX B300; AMD Instinct MI300X/MI325X; AMD Instinct MI300A | WG | — | North America | 2026-11-09 |
| CoolIT Systems | CDU · D2C · Sidecar · Manifold | 3,0001 | — | NVIDIA Vera Rubin (CHx3000); AMD Helios (CHx3000); NVIDIA GB200 NVL72 (CHx2000: up to twelve 120 kW racks) | WG | Ecolab | North America | 2026-11-09 |
| Cooler Master | CDU · D2C · Sidecar · Manifold | 2,5001 | — | — | WG | — | Asia-Pacific | 2026-11-09 |
| Motivair by Schneider Electric | CDU · D2C · RDHx · Sidecar | 2,5001 | — | NVIDIA (CDUs stated as certified for NVIDIA's latest hardware); NVIDIA NVL144 (HDU sized 1:1) | WG | Schneider Electric | North America | 2026-11-09 |
| Boyd Thermal (Eaton) | CDU · D2C · Sidecar · Manifold | 2,3003 | — | — | WG | Eaton | Europe | 2026-11-09 |
| ZutaCore | CDU · D2C · D2C-2φ | 2,0001 | 1201 | NVIDIA GB200 Grace Blackwell (ZutaCore release); AMD, Intel and NVIDIA CPUs/GPUs (general support) | DE-2φ | — | North America | 2026-11-09 |
| JetCool (Flex) | CDU · D2C · Manifold · QD | 1,8001 | 3001 | — | WG | Flex | North America | 2026-11-09 |
| HPE (Hewlett Packard Enterprise) | CDU · D2C · OEM | 1,6003 | — | — | WG | — | North America | 2026-11-09 |
| Chilldyne | CDU · D2C · Manifold | 1,5001 | — | — | WG | — | North America | 2026-11-09 |
| Accelsius | CDU · D2C · D2C-2φ | 2502 | 2502 | NVIDIA H100; NVIDIA H200; NVIDIA B200; NVIDIA Grace CPU; AMD MI325X; AMD MI355X | DE-2φ | Innventure | North America | 2026-11-09 |
| AVC (Asia Vital Components) | CDU · D2C · Manifold | — | — | — | WG | — | Asia-Pacific | 2026-11-09 |
| Dell Technologies (PowerCool) | CDU · D2C · RDHx · OEM | — | 5041 | NVIDIA GB300 NVL72 (PowerEdge XE9712); NVIDIA B200 (PowerEdge XE9680L) | WG | — | North America | 2026-11-09 |
| Envicool | CDU · D2C · IMM-1φ · Manifold · QD | — | — | — | WG · DE-1φ | — | Asia-Pacific | 2026-11-09 |
| GIGABYTE (Giga Computing) | D2C · OEM | — | — | NVIDIA Vera Rubin NVL72 | — | GIGABYTE Technology | Asia-Pacific | 2026-11-09 |
| Lenovo Neptune | D2C · OEM | — | 1353 | NVIDIA GB300 NVL72 (Lenovo rack-scale system) | WG | Lenovo | Asia-Pacific | 2026-11-09 |
| Wiwynn | D2C · OEM | — | — | — | — | — | Asia-Pacific | 2026-11-09 |
- Technologies
- CDUCoolant distribution unit
- D2CDirect-to-chip cold plate
- D2C-2φTwo-phase direct-to-chip cold plate
- IMM-1φSingle-phase immersion tank
- IMM-2φTwo-phase immersion tank
- RDHxRear-door heat exchanger
- SidecarLiquid-to-air CDU
- ManifoldRack and row manifolds
- QDQuick-disconnect couplings
- OEMServer maker with liquid-cooled racks
- FluidCoolant fluid supplier
- Coolant
- WGWater-glycol
- DE-1φSingle-phase dielectric
- DE-2φTwo-phase dielectric or refrigerant
Single-phase, two-phase and what feeds the plates
How ratings are readSingle-phase water-glycol
Most cold plates run water with propylene glycol (PG25 and similar), fed by a CDU. Designs differ at the plate: JetCool’s SmartPlate fires microjets of coolant straight at the chip’s hot spots, and Chilldyne runs its loop under negative pressure, so a leak pulls coolant away from the electronics instead of spraying it.
Two-phase cold plates
Two-phase plates boil a dielectric fluid or refrigerant on the chip and carry the heat away as vapour. A leak can’t short the server. Accelsius rates its NeuCool plates at 4,500 W+ per socket and its MR250 CDU at 250 kW on facility water up to 45 °C. ZutaCore’s HyperCool runs waterless, from a 20 kW air-based CDU up to 120 kW per rack.
Buy the loop, not just the plate
A direct-to-chip system is plates, rack manifolds, quick-disconnect couplings and a CDU. Check that the couplings follow the OCP UQD spec (Parker, Stäubli, CEJN and Danfoss sell UQD couplings, CPC sells blind-mate connectors) and that the CDU is rated at your facility water temperature. Supermicro, Dell, HPE and Lenovo sell the whole loop with the servers.